What size board do i need?

What size of main cable do i need, load is 3 x 100amp boards?? Main cable will be feeding a 4 way panel board.?

  • 3 x 100amp Boards 4 way Panel Board. I have a 3phase supply 100 feet away from my workshops, i need a main cable feeding the 4 way panel board which in turn will feed my 3 x 100amp Boards, Each Board will have 5 x 45amp MCBs.

  • Answer:

    UK or US?

Yahoo! Answers Visit the source

Was this solution helpful to you?

Other answers

If you are in the UK then this work falls under the scope of Building Regulations Part P. It must by law be carried out by a Registered professional electrician and a copy of the Test certificate submitted to your local Authority. The fact that you have to ask the question is evidence that you are not qualified or safe to do this job yourself. If you do it then you will be breaking the law and rendering your property insurance invalid. If you are in the USA then you must check the settings on your Yahoo Answers so that you restrict your questions to USA Only. You have sent it to the "UK & Ireland Only" section. Please correct this.

The Tank

Not enough info. What's the expected maximum demand? (How many machines going at once?) If there's only you in the shop, no chance that all those 100 A. boards will be anywhere near fully utilized. Do a load calculation for the shop feeder demand load. Use Watts or VA. from machine nameplates. 1 W/Sq. Ft for lighting, + any electric heat /AC, (one or the other, use largest of heating or cooling)+ your two largest machines, (or largest load running at any one time)+ any general load (small fridges etc.) + 10 KVA for 'headroom". For 3 Ph. 208V. 4W +G., take tot. VA./ 360 to get A. load req'd. In copper cable: .. in Alum. Cable: up to 60A. - #6 .... up to 50A.- #6 up to 80A. - #4 .... up to 75A - #4 up to 110A. #2 .... up to 90A. - #2 up to 150A. #1/0.. up to 120A. - #1/0 I doubt you'll need larger. Note, to meet Code, you'll need a driven ground, and a Main disconnect at that '4way' Shop distribution panel. If the 'shops' are separate structures a ground and single main disconnect for each structure.

Irv S

Find solution

For every problem there is a solution! Proved by Solucija.

  • Got an issue and looking for advice?

  • Ask Solucija to search every corner of the Web for help.

  • Get workable solutions and helpful tips in a moment.

Just ask Solucija about an issue you face and immediately get a list of ready solutions, answers and tips from other Internet users. We always provide the most suitable and complete answer to your question at the top, along with a few good alternatives below.