The phase voltage of a Y-connected three-phase generator is 120 V. What is the phase voltage of the load?

  • i am getting confused can some account for that to clear some confusions.1For a Y-connected generator with a -connected load, the phase voltage of the generator is 120 V. What is the voltage across each phase of the load? 2.The phase voltage of a three-phase, three-wire, -connected ac generator is 300 V. What is the line voltage? what do u look at when answering some of this questions

  • Answer:

    1) In this configuration, the load phase voltage would be 120v. 2) In a Y-connected generator, if the phase voltage is 300v, the line (or line to line) voltage would be square root of 3 * 300, 1.73 * 300v = 519v

anomlous at Yahoo! Answers Visit the source

Was this solution helpful to you?

Other answers

1) In this configuration, the load phase voltage would be 120v. 2) In a Y-connected generator, if the phase voltage is 300v, the line (or line to line) voltage would be square root of 3 * 300, 1.73 * 300v = 519v